Titel:
Titel:
Radon sensor networks for large buildings: balancing the trade-off between energy efficiency and health
Autoren:
Autoren:
Röttger, Stefan, Physikalisch-Technische Bundesanstalt (PTB), Fachbereich 6.1, Radioaktivität, ORCID: 0000-0002-4750-9563
Nötzel, Ralf, Universität Siegen, Siegen, GERMANY
Honig, Anja, Physikalisch-Technische Bundesanstalt (PTB), Fachbereich 6.1, Radioaktivität, ORCID: 0009-0007-9744-9822
Sabot, Benoit, Université Paris-Saclay, CEA, List, Palaiseau, France, ORCID: 0000-0003-3043-8006
Weinberg, Kerstin, Universität Siegen, Siegen, GERMANY, ORCID: 0000-0002-2213-8401
Beitragende:
Beitragende:
HostingInstitution: Physikalisch-Technische Bundesanstalt (PTB), ISNI: 0000 0001 2186 1887
Seiten:
Seiten:
12
Sprachen:
Sprachen:
en
DOI:
DOI:
10.7795/120.20250711
Art der Ressource:
Art der Ressource:
PTB: Zeitschriftenartikel, DINI: Article, DataCite: JournalArticle
Verlag:
Verlag:
Physikalisch-Technische Bundesanstalt (PTB)
Rechte:
Rechte:
https://creativecommons.org/licenses/by/4.0/
CC BY 4.0
Beziehungen:
Beziehungen:
IsIdenticalTo: DOI 10.1515/teme-2025-0036
Datumsangaben:
Datumsangaben:
Verfügbar: 2025-07-11
Klassifikationen:
Klassifikationen:
OCIS 120.0120 Instrumentation, measurement, and metrology ; PACS 23 Radioactivity
Datei:
Datei:
Datei herunterladen (application/pdf) 2.0 MB
MD5 Prüfsumme: f20c85a02a7ce7be3865eaaa67d3655b
SHA256 Prüfsumme: e7065f327021d76e8c95675709b3aed692bf942fba811e84f1be68b89dfb1556
Stichwörter:
Stichwörter:
Radon ; low-level activity concentration ; Radon- NET ; pulse ionization chamber
Zusammenfassung:
Zusammenfassung:
Radon 222 is a radioactive noble gas that is formed in the decay of the primordial 238U decay chain, with an average abundance of 3 parts per million (3 g ⋅ t-1) in the earth's crust. Since radon is the only noble gas in the decay chain, it has with its half live T12 = 3.8232(8) d, the ability to emanate from the ground or building materials and to interfere with the biosphere. Taking into account Directive 2013/59/Euratom, the EURAMET EPM project RadonNET was founded to find a trade-off between energy efficiency and health effects by means of measurements with small uncertainties. With this in mind, an pulse ionization chamber for the time-resolved measurement of radon activity at low concentrations is described here. The solution shown is characterized by low sensitivity to room and impact noise. Experimental investigations show the properties of the pulse ionization chamber under various conditions, particularly with regard to its use in sensor networks in larger buildings or future cities.
Zitat:
Zitat:
Röttger, Stefan, Nötzel, Ralf, Honig, Anja, Sabot, Benoit and Weinberg, Kerstin. "Radon sensor networks for large buildings: balancing the trade-off between energy efficiency and health" tm - Technisches Messen, 2025. https://doi.org/10.1515/teme-2025-0036
Förderung:
Förderung:
European Commission (EC), ISNI: 0000 0001 2162 673X, Grant Title: Radon metrology: Sensor networks for large buildings and future cities, Grant Number: 23IND07 RadonNET

Autoren

Röttger, Stefan, Physikalisch-Technische Bundesanstalt (PTB), Fachbereich 6.1, Radioaktivität, ORCID: 0000-0002-4750-9563
Nötzel, Ralf, Universität Siegen, Siegen, GERMANY